CH
CalcHub

Voltage Drop Calculator

Voltage drop is the loss of electrical pressure over distance. Too much drop causes dim lights, overheating motors, and tripped breakers. NEC recommends keeping voltage drop under 3% for branch circuits.

Enter Your Measurements

Results

Enter your measurements to see results

How to Use This Calculator

  1. Select your source voltage.
  2. Enter the load current in amps.
  3. Enter the one-way wire distance in feet.
  4. Select the wire gauge.
  5. Select single or three phase.

How Voltage Drop Calculation Works

Electrical resistance in wire causes voltage to drop as current travels the length of the conductor. Longer runs, smaller wire, and higher current all increase voltage drop. NEC recommends a maximum of 3% drop for branch circuits and 5% total (feeder + branch). Copper wire resistance values are from NEC Table 9 at 75°C. For aluminum conductors, multiply resistance by approximately 1.6.

Formula

Single phase: V_drop = 2 × Length × Current × Resistance per 1000ft ÷ 1000. Three phase: V_drop = √3 × Length × Current × R/1000ft ÷ 1000. Percentage = V_drop ÷ Source Voltage × 100.

Frequently Asked Questions

How much voltage drop is acceptable?
NEC recommends max 3% for branch circuits and 3% for feeders, with 5% combined total. For sensitive equipment like motors or electronics, keep it under 2%.
Does voltage drop matter for short runs?
Generally no for runs under 50 feet at normal residential currents. It matters significantly for long subpanel feeds, EV charger runs (40–60A over 50+ feet), and outdoor lighting circuits.
How do I reduce voltage drop?
Use larger wire (lower AWG number), shorten the wire run, or reduce the load current. Increasing voltage (240V vs 120V) also cuts percentage drop in half for the same power delivery.