Superheat & Subcooling Calculator

Superheat and subcooling measurements tell you whether an HVAC system has the correct refrigerant charge. This calculator converts your pressure readings to saturation temperatures and computes both values.

Enter Your Measurements

Results

Enter your measurements to see results

How to Use This Calculator

  1. Attach gauges and record suction and liquid line pressures.
  2. Measure suction line and liquid line temperatures with a clamp thermometer.
  3. Select your refrigerant type.
  4. Review superheat and subcooling values.

How Superheat/Subcooling Calculation Works

Refrigerant has a known relationship between pressure and boiling/condensing temperature (the P-T chart). By measuring pressure, we know the saturation temperature. Superheat is how much warmer the suction gas is above its boiling point — it should be 5–15°F. Subcooling is how much cooler the liquid line is below its condensing point — it should be 8–14°F. Values outside these ranges indicate charge problems, airflow issues, or restrictions.

Formula

Superheat = Suction Line Temp − Evaporator Saturation Temp (from P-T chart). Subcooling = Condenser Saturation Temp − Liquid Line Temp.

Frequently Asked Questions

What's the target superheat for a TXV system?
5–10°F at the evaporator outlet. TXV systems regulate superheat, so subcooling is the primary charging method — target 8–14°F subcooling (check manufacturer specs).
What does high superheat mean?
High superheat (>15°F) usually means the system is undercharged, has restricted refrigerant flow, or has excessive airflow across the evaporator. The refrigerant is boiling off too early.
What does high subcooling mean?
High subcooling (>20°F) usually means the system is overcharged or has a liquid line restriction. Too much liquid refrigerant is stacking up in the condenser.